Everest-S (HVSS-CC-S) High voltage trefoil cable cleat with closed centres. (Fixed and sliding base variants available).

CMP Everest-S trefoil cable cleat range has been designed for the safe retention of high voltage cables. The Everest-S is designed, constructed and tested in accordance with the International Standard IEC 61914: Cable cleats for electrical installations; to ensure the securing and retention of cables without sustaining damage to the cable(s). The S version of this product is designed to be used with smaller cables of size 52mm up to 100mm diameter. For larger cables please see the Everest HVSS-CC product range.
The Everest-S trefoil range of cable cleats are designed for use with high voltage cable installations and are manufactured to suit a range of cable diameters, or to suit specific project parameters.

The Everest-S cleat is designed to secure the cables in a trefoil formation to a mounting surface, providing excellent axial and lateral retention. This variation securely fixes the cables to a
support structure.

HVSS-CC-S cleats are fabricated in non-magnetic 316L stainless
steel.

Flame retardant low smoke and fume fixed liners are fitted as standard, helping to:

  • Restrain the cables within vertical applications.
  • Provide a layer of protection to both the cable sheath and the cable cleat, during normal operation where thermal elongation of cable occurs.
  • Protect the cable from chafing on any mounting surface due to differential movements, such as those found in marine and offshore applications.
  • Assist in the extra protection of cables in the event of short circuit fault condition

Features

  • Third party certification to IEC 61914
  • Available in 316L stainless steel
  • Sunlight (UV) resistant
  • Operating temperature -60°C to +90°C
  • Available in slide or fixed design
  • Excellent axial and lateral load retention
SHORT CIRCUIT TESTING TO IEC 61914 - CLAUSE 9.5
TREFOIL FORMATION
One Short Circuit 1.4m, with intermediate restraintsTwo Short Circuit 1.4m, with intermediate restraints
142mm conductor centres142mm conductor centres
1 sec1 sec
238kA Peak164kA Peak
92 kA r.m.s64 kA r.m.s.
Type 6.1.3 Composite
Design Specification IEC 61914
Temperature for permanent application -60°C to +90°C
IEC 61914 clause / part 6.2
Needle Flame Test Pass - 120 seconds
IEC 61914 clause
10.0, 10.1, IEC 60695-11-5
Impact Resistance Pass - Very Heavy
IEC 61914 clause 6.3, 6.3.5, 9.2
Material 316L Stainless Steel
Material Thickness 2mm
Liner Material FR LSF / LSOH Polymer
Cable Formation Trefoil
Jump to technical illustration    Fixing Pack Information

Product Selection Table

HVSS-CC
Part No.
Cable Ø RANGE
TAKE (mm)
DIMENSIONS mmWeight (g)
W1W2H1H2DPD1
HVSS-CC-052060-S52-601581731241371001302 x M121131
HVSS-CC-059066-S59-661661841351481001422 x M121200
HVSS-CC-062070-S62-701721911421561001502 x M121246
HVSS-CC-068076-S68-761802031541671001622 x M121317
HVSS-CC-074083-S74-831892171671801001762 x M121400
HVSS-CC-081088-S81-881962221761891001862 x M121451
HVSS-CC-086091-S86-912002281821951002022 x M121486
HVSS-CC-090100-S90-1002132411982121002152 x M121572

Technical Illustration